Default got a AC problem

so i have this leak at the port where ya put in the refrigerant. so i have low refrigerant causing my AC compressor to run way more frequently than it should. i was told by friend that its alright to unplug the power from the compressor so it wont kick on. i wanted to find out if thats alright, if it will damage anything. at least untill i can get it fixed. thanks guys
 
  #2  
Old 03-07-2010, 01:25 PM
RAW's Avatar
RAW
RAW is offline
Administrator

iTrader: (1)
Join Date: Aug 2009
Location: Alberta
Posts: 6,218
Received 684 Likes on 549 Posts
Default

It won't damage anything, unless the wire harness hits ground, then it might pop a fuse. It will be safe to unplug it, but is probably easier, quicker, and safer to pull the A/C fuse or Relay.
The downside to no A/C is no cold air, and no dry air for defrost.
 
  #3  
Old 03-07-2010, 06:12 PM
Ed ke6bnl's Avatar
Diesel Fan
Join Date: Apr 2008
Posts: 80
Received 3 Likes on 3 Posts
Default

If you can charge the ac and put a cap on to help prevent the leak you are good to go. You could have some dirt in the shraeder valve and some times a quick push and let go can free it as is the case on a tire valve. watch your eyes and hands be careful. It is a good idea if you disconnect it to energize it on at times to lube the seal BUt it will only cycling on if there is enough refrigerant to close the low pressure switch. Good luck Ed
 
  #4  
Old 03-07-2010, 06:53 PM
psy_6att_6ica_6's Avatar
Diesel Enthusiast
Thread Starter
Join Date: Apr 2009
Location: NORTH IDAHO
Posts: 237
Likes: 0
Received 4 Likes on 4 Posts
Default

so does that mean if i use the defroster it will fog the windows. i mean. this sint a big deal, it jut kicks on and off alot when idleing. ya, i had my heater core done last fall and thats when they found the leak. it has a cap on it. the guy tried to fix it, but it is leaking, something broke on it. i dont mind not having the AC, i just drive with the windows down anyway. but if its going to fog my windows or something ill just leave it be
 
  #5  
Old 03-07-2010, 09:10 PM
RAW's Avatar
RAW
RAW is offline
Administrator

iTrader: (1)
Join Date: Aug 2009
Location: Alberta
Posts: 6,218
Received 684 Likes on 549 Posts
Default

It won't be as efficient as it would with the system charged. The air won't be dried by the evaporator, it will have the same humidity in it as outside air. If it does start fogging up, roll down the window a bit. That will keep the humidity level low, but keep heat on your windshield.
 
  #6  
Old 03-08-2010, 10:30 AM
WLR-75409's Avatar
Diesel Fan
Join Date: Feb 2010
Location: Leander, Tx
Posts: 16
Likes: 0
Received 0 Likes on 0 Posts
Default

I've got two parts to this...
My a/c has sprung a leak that I cannot find (I have dye in the system and have used the special light and glasses, to no avil) Any suggestions would be great!
Second part: since the a/c is TU, I pulled the relay and stashed it away. No compressor, no dangling wires and no problems.
 
  #7  
Old 03-09-2010, 07:53 AM
RAW's Avatar
RAW
RAW is offline
Administrator

iTrader: (1)
Join Date: Aug 2009
Location: Alberta
Posts: 6,218
Received 684 Likes on 549 Posts
Default

My a/c has sprung a leak that I cannot find (I have dye in the system and have used the special light and glasses, to no avil)
Were you running the A/C compressor when you had the dye in the system?

If you can get your hands on a bottle of nitrogen and a regulator, fill the system with that. To about 100PSI, and use a spray gun of soapy water at all the connectors.
 
  #8  
Old 03-09-2010, 08:45 AM
chpmnsws6's Avatar
BOMBARDIER
Join Date: Feb 2008
Posts: 207
Likes: 0
Received 9 Likes on 8 Posts
Default

They also have the leak detector sniffers which seem to work fairly well
 
  #9  
Old 03-09-2010, 12:04 PM
WLR-75409's Avatar
Diesel Fan
Join Date: Feb 2010
Location: Leander, Tx
Posts: 16
Likes: 0
Received 0 Likes on 0 Posts
Default

Originally Posted by RAWilliams
Were you running the A/C compressor when you had the dye in the system?

If you can get your hands on a bottle of nitrogen and a regulator, fill the system with that. To about 100PSI, and use a spray gun of soapy water at all the connectors.
Now this may be a stupid question: can I just use the air compressor to charge the system?
 
  #10  
Old 03-09-2010, 07:06 PM
RAW's Avatar
RAW
RAW is offline
Administrator

iTrader: (1)
Join Date: Aug 2009
Location: Alberta
Posts: 6,218
Received 684 Likes on 549 Posts
Default

I thought that question might come up. You can, BUT.... compressed air is dirty and has moisture in it. Nitrogen is dry, and just nitrogen. I don not suggest compressed air, but if that's all you have it will work. In either situation when the leak is fixed, one should pull a vacuum on the system to remove any impurities, then charge with the appropriate freon.
 
Related Topics
Thread
Thread Starter
Forum
Replies
Last Post
burndiesel
24 Valve 2nd Gen Dodge Cummins 98.5-02
10
02-07-2023 01:15 AM
Jake9473
Ford Powerstroke 94-98 7.3L
7
07-22-2018 08:19 AM
jeremy01995
12 Valve 2nd Gen Dodge Cummins 94-98
1
09-14-2015 06:34 PM
thurobred1320
12 Valve 2nd Gen Dodge Cummins 94-98
2
05-05-2015 09:26 PM
Dadslb7
General Diesel Related
1
12-09-2014 11:05 PM



Quick Reply: got a AC problem



All times are GMT -5. The time now is 01:25 AM.